. ® POWER SYSTEMS, INC. Owner’s Manual GTS “W” Type Automatic Transfer Switch 200 Amp, 250 Volts Model Nos. 004635-1 004635-2 This manual should remain with the unit.

Also read the instructions and information on tags, decals, and labels that may be affixed to the transfer switch. Replace any decal or label that is no longer legible. Connection of a generator to an electrical system normally supplied by an electric. Never work on this equipment while physically or mentally fatigued. Keep the transfer switch enclosure door closed and bolted at all times.

Only qualified personnel should be permitted access to the switch interior. In case of an accident caused by electric shock, immediately shut down the source of electrical power. Generac recommends a copy of the SAFETY RULES are made and posted near the transfer switch. Also, be sure to read all instructions and information found on tags, labels and decals affixed to the equip- ment. Never install a transfer switch that has been damaged. Install the transfer switch as close as possible to the electrical loads that are to be connected to it. Mount the switch vertically to a rigid supporting structure.

After tightening terminal lugs, carefully wipe away any excess corrosion inhibitor. All power cables should enter the switch next to the transfer mechanism terminals. Use a torque wrench to tighten the conduc- tors, being sure not to overtighten, or dam- age to the switch base could occur. Step 1: With the handle attached to the actuating shaft, move handle in the direction of the arrow on the switch cover until it stops — DO NOT FORCE. Release handle slowly to allow the spring in the switch box to relax. Section 3 — Operation Generac GTS “W” Type Transfer Switch 3.

When certain that UTILITY supply voltage is cor- rect and compatible with transfer switch ratings, turn OFF the UTILITY supply to the transfer switch. Toyota avalon manual pdf. On the generator panel, set the AUTO-OFF- MANUAL switch to MANUAL position. Set the generator’s main circuit breaker (CB1) to its OFF or OPEN position. Set the Auto/Off/Manual switch to the OFF posi- tion to shut down the generator. NOTE: Do NOT proceed until generator AC output voltage and frequency are correct and within stated limits. Section 4 — Mounting Dimensions Generac GTS “W” Type Transfer Switch Mounting Dimensions – Drawing No. 0D3714-B Generac ® Power Systems, Inc.

Section 5 — Electrical Data Generac GTS “W” Type Transfer Switch Interconnection Diagram - Drawing No. 074106-B LOAD LOAD UTILITY UTILITY Generac ® Power Systems, Inc. Section 5 — Electrical Data Generac GTS “W” Type Transfer Switch 200 Amp, 2-pole Switch – Drawing No.

0D3819-A WHITE LEGEND C - CONTACTOR ACTUATING COIL GTS - TRANSFER SWITCH CONTACTOR TR - RELAY, TRANSFER TS - TERMINAL STRIP (CUSTOMER CONNECTION). 200 Amp, 2-pole Switch – Drawing No. 0D3819-A Section 5 — Electrical Data Generac GTS “W” Type Transfer Switch Generac ® Power Systems, Inc. Section 5 — Electrical Data Generac GTS “W” Type Transfer Switch 200 Amp, 3-pole Switch – Drawing No. 0D3818-A WHITE LEGEND C - CONTACTOR ACTUATING COIL GTS - TRANSFER SWITCH CONTACTOR PM - POWER MONITOR, 3 PHASE UTILITY TR - RELAY, TRANSFER.

Section 5 — Electrical Data Generac GTS “W” Type Transfer Switch 200 Amp, 3-pole Switch – Drawing No. 0D3818-A Generac ® Power Systems, Inc. Section 6 — Exploded Views and Parts List Generac GTS “W” Type Transfer Switch 200 A, 2Pole Switch Assembly – Drawing No. 0E2868$-D 0A9949-S 14 Generac ® Power Systems, Inc. 0A9949-T 0A9949 0A9949-T 0A9949 0C7907H-S 0C7907H-S 0C7907H-S 0A9949-S 0 0. INSTALL ACROSS E & N TERMINALS.INSTALL ON FRONT OF THE COVER (ITEM #20) Section 6 — Exploded Views and Parts List Generac GTS “W” Type Transfer Switch 200 A, 2Pole Switch Assembly – Drawing No. 0E2868$-D QTY.

DESCRIPTION XFER SW-W 200A600V2P LUG SLDLSS 400-#4X1/4-20 CU7AL SCREW FHM M8-1.25 X 20MM CR. Section 6 — Exploded Views and Parts List Generac GTS “W” Type Transfer Switch 200 A, 3-pole Switch Assembly – Drawing No.

0E4312$-F 0A9949-S 16 Generac ® Power Systems, Inc. C7907D C7907D-S A9949-S A9949 0A9949-S 0A9949. INSTALL ACROSS E & N TERMINALS.INSTALL ON FRONT OF THE COVER (ITEM #20) Section 6 — Exploded Views and Parts List Generac GTS “W” Type Transfer Switch 200 A, 3-pole Switch Assembly – Drawing No. 0E4312$-F QTY. DESCRIPTION XFER SW-W 200A600V3P LUG SLDLSS 400-#4X1/4-20 CU7AL SCREW FHM M8-1.25 X 20MM CR. NOTE: ALL UNITS MUST HAVE A START-UP INSPECTION PERFORMED BY AN AUTHORIZED GENERAC DEALER.

For a period of two (2) years or two thousand (2,000) hours of operation from the date of sale, which ever occurs first, Generac Power Systems, Inc. Will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below.

Gts

. 100 - 400 Amps, Automatic Transfer Switches 600 VAC 1 of 2. Standard time delay neutral will reduce switchover problems. Logic control with inphase monitor regulates switch functions and allows adjustable switch settings with LED indicators. Control switches located on the front of the door for ease of operation. All switches are UL 1008 listed and CSA certified. Electrically-operated, mechanically-held and interlocked main contacts with break before make design for fast, positive connections.

Rated for all classes of load, 100% equipment rated, both inductive and resistive with no derations. 2, 3, and 4 Pole 600 VAC contactors. 160 millisecond transfer time. Standard Features. Single coil design, electrically operated and mechanically held.

Programmable exerciser. SPDT auxiliary contacts.

Generac Gts Manual

Main contacts are silver alloy to resist welding and sticking. Conformal coating protects all printed circuit boards. Indicating LED's for switch position—Normal, Emergency, and Standby Operating. NEMA 1 enclosure with hinged door and key-locking handle.

Generac Gts 105

Terminal Lug Wire Ranges GTS RATED CONTACTOR TERMiNALS NEUTRAL BAR. GROUND LUG (1 LUG PER POLE) (1 PROVIDED) AMPS LUG WiRE RANGE # LUGS LUG WiRE RANGE LUG WiRE RANGE 100 2/0 – 14 AWG 2/0 – 14 AWG 2/0 – 14 AWG 150 400MCM – 4 AWG 350MCM – 6 AWG 350MCM – 6 AWG 200 400MCM – 4 AWG 350MCM – 6 AWG 350MCM – 6 AWG 300 600MCM – 4 AWG 600MCM – 4 AWG 350MCM – 6 AWG or 2 – 250MCM – 1/0 AWG 250MCM – 1/0 AWG. 350MCM – 6 AWG 400 600MCM – 4 AWG 600MCM – 4 AWG 350MCM – 6 AWG or 2 – 250MCM – 1/0 AWG 250MCM – 1/0 AWG. Not included in GTS with switched neutral.

Allowable wire range in brackets is for 2 wires per lug. Generac Power Systems, Inc. S45 W29290 HWY. 59, Waukesha, WI 53189. generac.com ©2010 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.

Bulletin 094700000S-A / Printed in U.S.A.